![]() |
Flow meter troubleshooting |
The following is essentially a reprint of the troubleshooting section in the flow totalizer manual. If you do not find what you need here, please contact us. We would like to make this section as useful as possible.
The resistance and voltage checks require a high input impedance multi-meter. We recommend the inexpensive digital electronic type such as the Fluke 73.
Please contact us if you are having problems that are not solvable with this table
|
Symptom |
Possible causes |
Suggested action |
|
No display |
|
Check power source and power cable. The fuse must be replaced at factory as a blown fuse may also indicate other damage. |
|
Display is dim |
|
Factory overhaul (Note: The older P750 board has a voltage offset potentiometer that could possibly correct this in the field) |
|
Counting is erratic |
|
Check ground on power cord and sensor cable, and check for corrosion in cables and connectors Check pump and line pressure. The flow rate should be at least 40 gallons per minute for the 2" turbine, 60gpm for the 3" turbine. Check the rotor (see below) Factory rebuild of turbine. A turbine can be rebuilt for about half the cost of a new one. |
|
Working, but not counting |
|
Check the rotor (see below) Check sensor (see below) |
While product is flowing, the AC voltage across the pickup pins should be above 30mV. Be careful not to short across the pins with product flowing as this could damage the sensor. If the voltage is low or erratic, there may be something resisting the flow of material across the turbine. This could be due to salting out of product or worn bearings in the turbine. If performance does not improve with cleaning, the turbine may be rebuilt.
The coil itself should be free of corrosion and have a resistance of about 1000W. A bad coil will have a resistance near zero or in the Megaohm range. Replace the magnetic pickup if there is corrosion or out of spec resistance values and retest the totalizer.
If the coil is good, set the meter to measure product 8, Test, (K-factor = 2) and pass a knife blade across the magnetic pickup. Counts should register on the meter. If they do not, check the connections magnetic pickup to cable and cable to meter (in the later case you will need to open the meter. Unplug it from the mains first). Note: K-factor should be 36 for P752 boards.